1. The Polymer manifold for floor systems enables parallel feed of terminal fluidic terminals.
2. Limited dimensions that enable the insertion in boxes to be walled in partitioning walls
3. Manual or automatic on-off interception of the single circuits.
4. Adjustment of the flow in transit for balancing between the various circuits by means of flowmeters mounted on the manifold and equipped with incorporated adjustment valve.
5. Direct readout on flowmeter of the rate of flow in transit in the individual circuits
6. Possibility of checking the performance of the circuits by inserting thermometers.
7. Thermostatic interceptor valves. Flowmeters for reading the flow with incorporated adjustment valve. A pair of brackets for fixing internally the control boxes.
8. They have found to be particularly adapted for feeding low temperature circuits serving radiant floor heating.
9. For the correct installation of the polymer manifold provided with a flowmeter, refer to the explicit section of the present “installation” sheet.
Body: Polymer (Pa66 + 30%FV) Brass inserts on the parts threaded
Valve imperviousness: EPDM
Hand wheels and caps: ABS
Derivation connection: G 3/4” (ISO 228)
Eurokonus
Connections on line: Female 1" (ISO 228)
Max. working pressure: 8 bar
Max circuit test pressure: 10 bar (at 20°C temperature)
Differential pressure Δp max.: 1 bar
Temperature of use: from 5 to 80°C
Fluid allowed: Water or Water + glycol* 50%
Flowmeter: from 1 to 4 l/min
Flowmeter precision: ± 10%